Whole House Diagnostics and Repair
Contractors trained in "whole house diagnostics and repair"
understand the "house as a system"- the interrelationship of duct
leakage, house pressure, exhaust fans, duct pressures, back drafting, equipment
efficiency, insulation, ventilation, air tightness, moisture, and health
and safety.
A house is not static; it is more a complex organism of parts and pressure
at odds with themselves and rarely able to maintain equilibrium, driven
by improperly sized and poorly installed heating and air conditioning systems
inducing positive pressures in some zones and negative pressures in others
while dryers, vent-a-hoods, power roof vents, Jenn-Aire ranges and bathroom
vent fans actively exhaust air while furnace and water heater vent pipes
and the house itself behave like chimneys drawing outside air in through
penetrations in the crawlspace and the building envelope to replace conditioned
air being drawn up and out through partition walls, holes in the attic,
by-passes, cracks, chases and hundreds of both accidental and intentional
holes and penetrations in the ceiling, walls and floor from gas pipes, electric
wires, cable, telephone lines, and poorly fitting joints.
Because the house is a system, when one thing changes, something else is
effected. For instance, simply plugging holes and sealing ducts can create
worse problems than it fixes. Improper air sealing has resulted in fireplaces
not drafting, elevated radon levels, moisture problems, and the list goes
on. Why? The leaks that were sealed in the living room provided needed
combustion
air for the fireplace. Prior to sealing, the leaks in the basement supply
duct leaks were positively pressurizing the basement and keeping radon out,
but when sealed, the basement became negatively pressurized and radon and
moist, contaminated crawlspace air was drawn in.
In the house-as-a system approach, there are three interdependent components
that must be addressed if a house is to perform to its full potential: the
BUILDING ENVELOPE, the MECHANICAL SYSTEMS and the OCCUPANT.
In addressing the "building envelope," it is important to first
define where the air barrier will separate the "conditioned" and
the "unconditioned" spaces. This (hopefully) continuous air barrier
is typically defined by walls, ceiling, floor, doors and widows, but the
unique geometry of many buildings can make defining the envelope more
complex.
Second are the mechanical systems which include furnaces, air conditioners,
water heaters, vents, fans, blowers, clothes dryers and any other mechanical
device that moves air and induces pressures within the house.
Third is the occupant who closes doors, opens windows, sets the thermostat,
changes (or fails to change) furnace filters, and in dozens of ways unknowingly
prevents the building from performing at peak efficiency.
In whole house repair, "whole
house"
diagnostic energy inspectors and qualified
contractors usually address air sealing and insulating the building
envelope first, then the mechanical systems and finally the occupant. There
are exceptions. If a furnace has a cracked heat exchanger, or the house
has unvented gas heaters, these things should be addressed prior to sealing
a house. The furnace should be repaired or replaced and the unvented gas
heaters should be removed. Health and safety are always the first concerns
of a truly "qualified" contractor.
Qualified contractors use diagnostic tools like blower doors, digital pressure
gauges, pressure pans, Monoxers®, and Duct Blasters® for diagnosing,
repairing, and pressure balancing a home.
These contractors are able to measure and pinpoint air leakage in the ducts
and the building envelope before and after improvements. This allows them
to know what and where the problems are, formulate a plan of action, set
targets, know when the targets have been met, and test their way out of
a house to make sure it is left safe and healthy as well as comfortable
and more energy efficient.
To be listed as a "whole house"
diagnostic energy inspectors or a qualified
contractor, a contractor must have completed
training in the classroom and in the field from a recognized training
organization
specializing in state-of-the-art diagnostic and retrofit procedures.
If you believe you have the experience and training to be listed as a
"whole
house" diagnostic energy inspector or a qualified contractor, click
add me to list.
If you are interested in receiving training in whole house diagnostics and
repair, check out upcoming training classes.
Click here to order a diagnostic inspection.
Blower Doors
The blower door is a calibrated device built specifically to identify
and measure the overall leakage of a building and the duct system. The blower
door consists of a large fan which is mounted in a frame and placed in an
exterior door. The blower door is used to depressurize (or pressurize in
some cases) the house. Using the pressure readings and a computer, the leakage
of the house and ducts can be calculated.
A Duct Blaster, a small blower door designed specifically to test ducts,
can be used in new construction before the sheet rock covers the ducts.
Used with pressure pans, pressure gauges, and a blower door in existing
houses, the duct blaster can help determine the extent and location of hidden
duct leakage.
The blower door greatly enhances our view of the whole house as a system,
a complex interplay of temperatures, humidity, air movements, convection
and forced-air pressures induced by the air-handler of the central duct
system.
With the blower door testing, air leakage sites can be identified, the total
air change rate of the house can be determined, duct leakage can be measured
and located, and moisture, humidity, mold and mildew problems can be traced
to their source.
If you are interested in more information on blower doors or upcoming blower
door training, check out blower door
manufacturers
and training classes. If you are interested
in blower doors
Duct Leakage
Addressing duct leakage and the pressures in a house is a critical part
of whole house diagnostics and repair.
We have known for some time that improperly charged and improperly sized
mechanical equipment and/or undersized return and supply ducts can reduce
performance and shorten the life of heating and cooling equipment. We have
only recently started to realize how huge the problem of duct leakage is
and the enormous impact it has on system performance and heating and cooling
costs.
While the duct system may comprise only 5% to 7% of the total surface area
of the house, ducts are usually responsible for 18% to 30% of the total
leakage of the house. Studies show supply and return duct leakage in Florida
homes routinely triples a home's natural air exchange with the outside whenever
the cooling system is operating.
A report by Proctor
Engineering on the PG&E Appliance Doctor Pilot Project in Fresno,
California determined a 24.4% cooling energy savings and 12% heating savings
can be accomplished by a program that diagnoses and repairs duct leakage,
airflow, and overcharge on residential central air conditioners.
Bruce Davis' 1992 Arkansas study funded by the Arkansas Energy Office showed
an average 19% reduction in run time of gas furnaces and a 32% savings in
heat pump houses from only sealing ducts!
More important, are the implications for health and safety.
It is estimated that one house in six has at least one supply duct with
a major disconnection. When the blower for the central heating or cooling
system turns on, it pumps conditioned air out of the house through leaking,
improperly sealed or disconnected supply ducts. As air is pumped out and
is unable to return, negative pressures are created in zones of the house
where return air registers are located. The air lost to supply leaks must
be replaced by outside air. In a tight house, the easiest path for outside
replacement air may be down the chimney of the fireplace or vent stacks
of water heaters and furnaces. This draws carbon monoxide and other combustion
byproducts into the home environment.
These negative pressures can also draw in outside pollutants like mold and
mildew from a crawl space as well as radon and other sub-soil gasses from
under a slab or through the basement.
Leaky return cavities are probably the most common cause of outside air
usually from the attic or crawlspace being drawn into the return ducts and
pumped into the house. If there is more leakage on the return side than
the supply side, this will positively pressurize the house which forces
conditioned air out through cracks and holes of the building envelope where
air exchange would normally not occur.
Both situations happening at once are usually happening. Positive pressures
are causing exfiltration in bedrooms with closed doors while negative pressures
draw outside air into the zone where the returns are starving for air.
This is why pressure balancing a home is critical for peak performance and
health and safety, but it takes the right tools, good training and hands-on
experience to be successful.
Clues to Problem Houses
Uncomfortable houses or rooms.
- Uncomfortable houses or rooms that don't get warm enough in winter
or cool enough in summer can be the result of one or a combination of things:
air leakage, disconnected or improperly sized ducts, lack of insulation,
improperly sized equipment, lack of pressure balancing, inadequate
insulation,
the list goes on. There is no one answer; all houses are different. However,
a number of indicators of likely problems follow. If these are familiar,
seek the advice of a "qualified contractor."
Leaky return duct(s).
- Remove the return air grill in your house. It is probably located in
a central hall or under a stairway. Look inside. Do you see a well-sealed
and insulated duct or do you see studs and the back of sheetrock. If you
see studs and sheetrock, you are looking into a building cavity being used
as a duct. It is guaranteed not to be air tight. Its framing and the framing
of connected walls almost certainly provide a path for outside air to be
drawn into the house when the air handler turns on. There are no arrows
to tell the air where to go; it will take the path of least resistance
which will not all be neatly through the return air grill. If your return
is an unsealed building cavity, it is guaranteed that you have a problem.
Leaking supply ducts.
- On average, most building scientists agree that about one house in
six has at least one supply duct with a major disconnect. As air is pumped
out of leaking or disconnected supplies, the house at best becomes negatively
pressurized which increases infiltration, decreases comfort, and increases
costs. At worst, the return air duct which is now starving for air starts
back-drafting fireplaces, gas water heaters and gas furnaces, drawing in
carbon monoxide and other combustion by-products.
Single returns.
- How many return air ducts does your house have? Ideally, every room
should have a return duct. Some houses have a total of two; most houses
have only one return for the entire house. The result is uneven temperatures,
increased infiltration (and exfiltration), increased duct leakage, reduced
equipment efficiency, and increased chance of backdrafting of combustion
appliances.
Lack of pressure relief.
- For a house to operate at its best, all pressure zones in the house
should be balanced. The problem can come when a room, or block of rooms
like a bedroom at night is closed off. If the heating or cooling unit is
running, air is being put into the bedroom through the supply ducts, but
it can't get back to the return because the door is closed. The bedroom
becomes positively pressurized while the return zone starves for air.
When a house is properly pressure balanced, backdrafting of fireplaces,
gas water heaters and gas furnaces will not occur. When doors or closed
within the house, rooms will not become either negatively or positively
pressurized. All rooms will get the amount of air they need to ensure comfort
and even temperatures throughout the house.
Will undercutting doors relieve pressure?
- Maybe, but look at a master bedroom with a large bathroom and walk-in
closet. Add up the total square inches of the maybe four to six registers
and see how many inches you would have to undercut the door for equivalent
square inches and adequate pressure relief. The result wouldn't allow for
much privacy! Yet, there are a dozen ways to relieve pressure in a room
that are rarely used.
Fireplace won't draft.
- A fireplace that won't draft could be the result of several things.
It could be simply poor design with not enough height in the chimney or
a poor ratio of fireplace opening to chimney area. It could be obstructions.
Squirrel nests, bird nests and dead animals can all stop a fireplace from
drafting.
If the chimney is unobstructed and at least 16 feet tall, opening a window
in the room can provide combustion air and relieve the negative pressure.
If the fireplace now drafts, you have treated the symptom, but you really
haven't solved the problem. The problem is worse.
Close the window you just opened. Now turn on the clothes dryer and all
the vent vans. Close all doors except those between the fireplace and the
rooms with the vent fans and clothes dryer. Will the fireplace draft now?
How far must you open the window in the room with the fireplace now to
relieve the pressure? In a leaky, old house, probably not much. But in
a reasonably tight house,open it all the way and the fireplace may still
not draft.
Maybe the chimney works ok when you have a roaring fire, but what if it
is late at night and you close off the kids room and go to bed and let
the fire die out. A fire can start to backdraft as the fire dies down and
can no longer maintain draft. If the central heating system turns on, there
is now the possibility carbon monoxide will be distributed throughout the
house.
This is not as uncommon as one might think. As we build tighter and tighter
houses with combustion appliances located inside and disregard the pressures
that are induced by mechanical systems and the "stack effect"
of the house itself, we will continue to see more and more problems with
carbon monoxide, indoor air quality and health and safety.
With fireplaces or any other combustion appliance, if you must have it
inside the conditioned space, start by providing it with outside combustion
air.
Ducts in the attic or crawlspace.
- Where are your ducts? In the attic? The crawlspace? Between floors?
Where should they be? Heat moves in only one direction, from hot to cold.
And the greater the difference in temperature, the faster it moves.
The attic is the worst location for ducts. The attic is the same temperature
as the cold outside in the winter. In the summer its worse, the attic is
much hotter than outside. Trying to deliver 70 degree air through a duct
located in a 140 degree attic is like trying to wash your car with a soaker
hose- there may be a trickle of water coming out the end, but much of it
was lost along the way.
The crawlspace is better than the attic for ducts. The basement is better
yet. Furred down into the living space is best of all locations. If your
ducts are furred down into the living space, any cooling or heating loss
is lost to the conditioned space, so it is really not "lost."
Flex duct.
- If you have flex duct snaking around in the attic or under the floor,
it is a sign of a low-ball bid job. Flex duct is easily collapsed. The
spiral wire which gives it its shape creates added friction inside and
slows down air movement. It is typically underinsulated. If it has vinyl
outer cover and is exposed to sunlight, will break down and fall apart.
Duct tape.
- Called temporary tape, duct tape is a problem, particularly in areas
like a damp crawlspace or an attic where temperatures fluctuate. The one
place to not use duct tape is on ducts! Mastic is better. It goes on like
mashed potatoes, sets up and stops leaks for the life of the system.
Fiberglass ceiling insulation.
- Fiberglass does not stop air movement; that is why it is used for
filters.
If you see dirty spots around fiberglass insulation on ducts, in an attic
or under the floor, it indicates a place where the fiberglass has filtered
and trapped the dirt as air has passed through. Unless all penetrations
in the attic floor were first carefully sealed, blown fiberglass insulation
in the attic does not necessarily mean you have a well-insulated attic.
There are some new blown fiberglass insulation products with binders coming
into the market that have properties for stopping air leakage similar to
cellulose. Fiberglass batts, if carefully installed, can do a better job
of stopping air leaks in the attic than loose blown fiberglass.
The key words are "carefully installed." Be sure to carefully
fit batts around wiring and plumbing. In addition, they should be
cross-linked
in the attic, that is, batts should be laid between the joist until they
are higher than the joists, and the next layer should be laid in the opposite
direction. If you are adding additional insulation over fiberglass batts,
consider blowing cellulose for higher R-value and reduced air leakage.
Hiring a Contractor
- In screening contractors, the following are some questions you may
want to ask:
Do you build energy efficient houses?
- Most all builders say yes, but make sure. Ask for references. Agree
on the specifications for the home before you start, including pressure
relief in all rooms and air tightness of the building envelope and the
duct system. It will depend on the size and location of the house and the
number of occupants, but you will want to spec the finished house in the
range of 3.5-.4 natural air changes per hour.
Get your contractor to agree to have the ducts tested for air leakage prior
to the sheetrock covering them up. Get any combustion appliances like a
gas water heater or gas furnace outside the building envelope. If they
have to be located inside, supply adequate outside combustion air, insulate
the closet walls and use an airtight, insulated door to the closet. When
completed, have the house blower door tested to ensure health and safety,
comfort and maximum energy efficiency.
How energy efficient do you build?
- "Energy efficient" for an energy efficient mortgage means
the house meets the Model Energy Code (MEC). But remember, not all state
have adopted MEC. Most builders build to code, and while that may sound
good, what it also means is that the house is the least efficient allowed
by law.
- Get a home energy rating on the plans before you start. You will want
a house that exceeds the "minimum allowed by law." Try for an
energy rating of FIVE STAR and at least FOUR STAR PLUS for a new home,
and THREE PLUS to FOUR STAR if you are upgrading an existing home. See
ordering an energy rating.
Are you a member of the Energy Efficient Building Association?
- The Energy Efficient Building Association (EEBA)
is a national organization of builders and trade allies who specialize
in energy efficient construction that usually exceeds the minimum standards
of CABO/MEC. Membership in EEBA is a good indicator of an exceptional
builder.
EEBA is a leading provider of builder training in the area of resource
efficient design of homes and small commercial buildings. Founded in 1981;
now with over 500 members, EEBA works internationally to reduce energy
waste, improve resource efficiency and help the environment through better
builder training and direct member services.
Located in Minnesota, with a service bureau in Washington, DC, EEBA can
assist most home builders, remodelers or designers to produce more resource
efficient low-energy buildings that are healthy, comfortable, durable,
have excellent resale value, and help maintain environmental quality.
Can you explain the concept of a "house as a system?"
- Review "whole house" diagnostics
and repair on this site and judge your contractor's answer for yourself.
How tight should my house be?
- A natural air change rate of .35 to. 4 natural air changes per hour
(nach) is usually ideal for comfort and air quality, but it will vary with
the size of the house and the number of occupants. Remember, you will not
know for sure how tight your house is without measuring it!
How do you measure the tightness of a house?
- Blower door is the right answer, but
"tracer
gas" would gets high marks.
From the return grill to the supply registers, what is the maximum leakage
you can guarantee my ducts to be when you are finished?
- There should be NO leakage, but there will almost always be some because
of the way equipment is manufactured. For new installations, aim for a
maximum of 50cfm25 (that means 50 cubic feet of leakage per minute at 25
Pascals of pressure). For retrofit,75 to 100 cfm25 is pretty good.
How will you measure that?
- A Duct Blaster or a blower door are both good answers.
What is a Pascal?
- A Pascal is a unit for measuring pressure. 50 Pascals is about the
same as .5 inches of water column (heating and air conditioning talk).
What kind of insulation should I have blown into the walls of my old
house built with no insulation?
- Cellulose is preferable fro blowing side walls. It not only has higher
R-value than fiberglass or rock wool, but it stops air leaks.
What about walls of my new house?
- Wet spray cellulose is hard to beat. Same reasons as above, plus no
voids in the wall from wiring, plumbing, etc. However, some of the new
wet-blown fiberglass insulation products have similar properties to wet-blown
cellulose. Some foams may also be acceptable, but are usually
cost-prohibitive.
Use fiberglass or rock wool batts only if all penetrations in the wall
cavities are carefully sealed and a house wrap or exterior insulation
sheathing
is installed to further ensure air leakage reduction as the house moves
over time. If you use wet-blown cellulose, a house wrap is unnecessary.
How about insulation under my floor?
- Fiberglass batts under the floor are acceptable after sealing all
penetrations,
holes, openings, etc. Or, insulate the perimeter sidewalls with rigid
insulation
or wet blown cellulose and add a polyethylene ground cover to keep out
moisture.
How will my air conditioner be sized?
- Use a Manual J calculation or equivalent. WRONG ANSWERS include:
"One
ton per 500 square feet like dad used to" or "I've done enough
houses to eye-ball it." Don't assume you can simply replace it with
the same size as what's there. The existing one may not have been sized
correctly to begin with, and/or some things may have changed since it was
installed.
In doing your sizing calculation, what is the natural air exchange rate
you will use?
- Determining the air leakage of a home is a guess unless the house is
tested (like with a blower door). Most new houses average .5 to .6 natural
air changes per hour (nach). Older homes range from around one to two and
sometimes three; they vary a lot.
- For adding or replacing equipment in an older home, here's the rub.
If you install an air conditioner in a leaky uninsulated home it will have
to be huge. The next year, if you insulate and air seal, the unit will
then be oversized and won't run long enough to remove moisture. The result
is high humidity and discomfort. Always air seal and insulate first and
then size equipment!
Do you duct tape all your joints?
- If the contractor says "Of course!" it's the wrong answer.
Duct tape may still be the industry standard, but duct mastic is way better.
It goes on like mashed potatoes and it lasts. If the contractor says no,
we don't use duct tape, we use mastic, hire 'em! But check the work before
you pay. Peel back the insulation hiding several joints and make sure they
really did!
-
- Remember, you don't get what you expect, you get what you inspect!
Do you have other questions specific to your house or your project? Check
out our consulting services.
Please e-mail your comments and questions
to
.
Copyright © 1996 by RH&CO.
All rights reserved.